Skamania County PUD has two temporary services available, overhead and underground. During the site visit the Skamania PUD Representative will advise which route to take.
Overhead Temporary Service
- Provide the meter base, PVC conduit, support, conductor (up to the weather head/service mast) and paneling based on the size of service needed.
- Install temporary service pole within 30 feet of the transformer pole and no closer than 10 feet.
- Have meter base inspected and approved by the Washington State Department of Labor and Industries. Permit and inspection sticker must be displayed.
- Service drop conductor must maintain a minimum height of 12 feet over open space and 18 feet over driveways.
- Consult and electrician or Washington State Department of Labor and Industries Electrical Inspector for current NEC guidelines for service entrance, meter base and grounding codes.
- Once permanent service has been inspected, the PUD will de-energize the temporary service and remove the meter.

Underground Temporary Service
- Provide the meter base, PVC conduit, support, conductor and paneling based on the size of service needed (if temporary service is not located near a transformer, the PUD will provide and install the conductor at customer’s expense).
- Locate temporary service adjacent to but no closer than 3 feet from a Skamania County PUD pedestal or transformer with a minimum of at least 8 feet of extra conductor (measured at the transformer) for termination.
- Have meter base inspected and approved by the Washington State Department of Labor and Industries. Permit and inspection sticker must be displayed.
- Consult and electrician or Washington State Department of Labor and Industries Electrical Inspector for current NEC guidelines for service entrance, meter base and grounding codes.
- Once permanent service has been inspected, the PUD will de-energize the temporary service, abandon the underground conductor and remove the meter.